Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Mini Circuit Breaker >> DZ30LE-32 Residual Current Operated Circuit Breaker
 

 

 

 

 

 
1. Application
 
DZ30LE-32 is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V, used as electron shock protection. It can protect circuit form overload and short circuit. This product has advantages of small volume, high breaking capacity, live and zero wire are cut off at the same time, also protecting person from electric shock when the live wire connected opposite. It conforms with the standards of IEC61009.
 
2. Main Technical Parameter
 
Type DZ30LE-32
Pole
1P+N
Rated current (A)
6,10,16,20,25,32
Rated voltage(V)
230
Rated residual action current I△n(A)
0.03
Rated residual non-action current I△no(A)
0.015
Rated residual making/breaking capacity I△m(A)
500
Type of instantaneous release
C
Rated making/breaking capacity Im(A)
4500
 
3. Applicable conducting wire
 
Rated current(A) Norminal cross section of wire mm2
In ≤ 6
1
6< In ≤ 13
1.5
13 < In ≤ 20
2.5
20 < In ≤ 25
4
25 < In ≤ 32
6
 
4. Residual current breaking time
 
In (A) I△n (A) Breaking time(s) when equals to rating following
I△n 2I△n 5I△n 5,10,20,50,100,200,500a(A) I△tb
6-32 0.03 0.1 0.06 0.04 0.04 0.04
 
5. The over-current protection property
 
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
Cold position 1.13In t ≥ 1h Non-release -
30±2oC Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s < t < 60s Release Current smoothly rises to specified value within 5s
-5~+40oC Cold position 5In t ≥ 0.1s Non-release Type C
Cold position 10In t < 0.1s Release Type C
 
6. Dimension
 

 

 